Device Type
                                
                                
                                    24 V DC Solenoid coils
                                
                             
                            
                                
                                    On State Output rating
                                
                                
                                    100 mA continuous @ 24 V DC
                                
                             
                            
                                
                                    Off-state Leakage Current
                                
                                
                                    1 mA maximum
                                
                             
                            
                                
                                    Line Fault Detection
                                
                                
                                    Guaranteed short circuit: <50 Ω Load, Guaranteed good status: 240 Ω to 10 kΩ load, Guaranteed open circuit: >20 kΩ load
                                
                             
                            
                                
                                    Configurable Output Behavior
                                
                                
                                    Momentary Output, Continuous Pulse Output, Line fault testing
                                
                             
                            
                                
                                    Line Fault Test Timing
                                
                                
                                    200 µsec
                                
                             
                            
                                
                                    Field Circuit Protection
                                
                                
                                    200 mA Current Limiting Circuit, Field wiring disconnect
                                
                             
                            
                                
                                    CHARM power req.
                                
                                
                                    116 mA max @ 24 V DC - Standard Terminal Block, 24 mA max @ 24 V DC - Relay Output Terminal Block
                                
                             
                            
                                
                                    CHARM Heat Dissipation
                                
                                
                                    Pulse Count - Pulse train 0.1 Hz to 10 KHz, 50 µsec min pulse width