Sensor Type
V AC Inductive load
Output Range
20 to 250 V AC
Output Rating
0.5 A continuous (10 A inrush for < 20 ms, 2.5 A inrush for < 100 ms)
Off State Leaking Current
2 mA maximum at 120 V AC, 4 mA maximum at 230 V AC
Configurable Output Behavior
Momentary Output, Continuous Pulse Output
Isolation
Each channel is optically isolated from the system at 250 V AC
Field Circuit Protection
Field wiring disconnect, Recommend external fuse at power source
CHARM power req.
12 mA max @ 24 V DC
CHARM Heat Dissipation
0.70 W