Sensor Types
                                
                                
                                    NAMUR Sensors, Dry Contacts
                                
                             
                            
                                
                                    Detection level for ON
                                
                                
                                    >2.1 mA
                                
                             
                            
                                
                                    Detection Level for Off
                                
                                
                                    <1.2 mA
                                
                             
                            
                                
                                    Channel Impedance
                                
                                
                                    1kOhm ±10%
                                
                             
                            
                                
                                    Wetting Voltage
                                
                                
                                    8V DC ±1V DC
                                
                             
                            
                                
                                    Fault Detection capable
                                
                                
                                    NAMUR Sensors or field resistor pack, Guaranteed short circuit: <100 Ω , Guaranteed good status: 360 Ω to 20 kΩ , Guaranteed open circuit: > 75 kΩ
                                
                             
                            
                                
                                    Isolation
                                
                                
                                    Galvanically isolated according to EN 60079-11. Voltage peak value 375V DC.
                                
                             
                            
                                
                                    CHARM power req.
                                
                                
                                    28 mA max @ 24V DC ±10%
                                
                             
                            
                                
                                    CHARM Heat Dissipation
                                
                                
                                    0.57 W
                                
                             
                            
                                
                                    Configurable channel type
                                
                                
                                    Dry contact or discrete state sensor changing <2 Hz